The Slow Discharge: Reading DC Link Capacitor Health Before the Trip

Bosch Motors & Controls UK
The Slow Discharge: Reading DC Link Capacitor Health Before the Trip

Photo: Suyash.dwivedi, CC BY-SA 4.0, via Wikimedia Commons

A drive that trips on DC bus overvoltage during deceleration, then runs perfectly for a fortnight, is not necessarily a drive with a control problem. It may be a drive whose DC link capacitance has fallen far enough that the same braking energy now produces a larger voltage rise. The symptom looks intermittent. The mechanism is monotonic.

This article sets out what actually ages inside the DC link of a Bosch drive, why visual inspection reaches its limit early, and how to build an evidence-based routine that flags degradation while the machine is still available for planned work.

What ages inside the DC link

Most drives in the field use aluminium electrolytic capacitors in the DC link, chosen for energy density and cost. Inside the can, a liquid electrolyte saturates a separator and makes contact with the anode foil. Over time, the electrolyte escapes — through the seal, by diffusion, accelerated by heat and by the current that passes through it. Capacitance falls. Equivalent series resistance, ESR, rises.

The two effects compound. Higher ESR produces more internal heating for a given ripple current; more heat drives further electrolyte loss. The relationship is broadly Arrhenius-like, and the practical rule quoted by most manufacturers still holds: every 10 K reduction in operating temperature roughly doubles expected life. That single sentence explains why cap failures cluster on drives in hot cabinets, in clogged enclosures, or mounted high in a plant room where the ambient stratifies.

Some drive families use film capacitors in the DC link on selected ratings. Film capacitors age differently and generally more slowly, but they are not immortal and they are not immune to termination fatigue. Do not assume a construction; establish it from the drive documentation before designing a monitoring regime.

Ripple current: the load you cannot see on the display

The DC link carries a pulsating current at six times the supply frequency, plus a switching-frequency component from the inverter, plus whatever the load imposes. The capacitor must absorb the difference between what the rectifier delivers and what the inverter draws. The resulting RMS ripple current heats the capacitor, and the hotspot temperature — not the case temperature — is what governs life.

Ripple current rises with output current and with low modulation index, so drives running at low output frequency with high torque demand are disproportionately stressed. This is why some of the hardest-worked DC links in a plant are not on the biggest machines but on the ones doing high-torque, low-speed work, or running frequent acceleration cycles with regenerative braking.

Why visual inspection runs out of road

Inspection has value, but late value. Bulging cans, electrolyte residue, crusted deposits at the vent, discolouration of the board beneath — these are end-of-life indicators. By the time they appear, the drive is already close to a failure, and the opportunity to plan the intervention has largely gone. Equally important, a significant proportion of degrading capacitors give no external sign at all. A clean, flat, dry capacitor can still have lost 30 % of its capacitance.

Inspection also requires access, and access to a DC link means a shutdown, a safe isolation, a verified dead test and a discharge wait. If you are going to spend that, spend it collecting a measurement as well.

Build the baseline at commissioning

Every condition-monitoring routine is worth exactly what its baseline is worth. At commissioning — or at the first planned outage of an existing drive — record four things at a defined reference condition:

These four numbers turn every subsequent check into a comparison rather than a judgement call.

The three measurements that matter

Ripple voltage under load. With the drive running at a repeatable load point, measure DC bus ripple with a differential probe of adequate voltage rating and bandwidth. Ripple rises as capacitance falls, so a trend of increasing peak-to-peak values at constant load is the clearest single indicator of degradation. Confirm the probe and scope combination is rated for the bus voltage with margin, and never use a single-ended probe on a live DC bus.

Discharge time. After isolation, measure the time for the DC bus to fall from its nominal value to a safe threshold through the drive's internal discharge path. Since the discharge follows an exponential with a time constant proportional to capacitance, a lengthening discharge time is a direct indication of capacitance loss. It is also a safety check in its own right: if the drive takes longer to fall below the safe threshold than the manufacturer's stated wait time, that wait time is no longer valid for your site and must be escalated immediately.

Thermal context. Log cabinet inlet temperature and, where accessible, the temperature near the capacitor bank. A rising capacitor temperature at constant load means rising ESR. A rising cabinet temperature means the thermal margin that was designed in has been eaten by a clogged filter, a failed fan or a changed plant room.

Screening a fleet without stripping every drive

A fleet of drives cannot all be scoped on the same afternoon. Rank them instead. Weight by running hours, by cabinet ambient, by proportion of time at high load, by brake or regenerative duty, and by age. The top decile gets the full three-measurement routine in the next planned outage. The remainder get ripple voltage checks at a fixed reference load and an annual thermal review.

This is also where the drive's own diagnostics earn their place. Many platforms log DC bus undervoltage or overvoltage events, pre-charge relay faults and bus-related trips. A drive accumulating bus trips that were dismissed as supply dips deserves a look at its capacitors, not another conversation with the electricity supplier.

Note the interaction with other causes. A 4 % supply imbalance raises ripple current; a failing pre-charge contactor raises inrush stress; a hot cabinet shortens everything. Correct those first, or the capacitor routine will simply document a problem you are actively making worse.

Replace the capacitor bank or the drive?

Where a drive is supported, capacitor replacement is a legitimate option and often the cheapest path for a large or specialised unit. Where spares are not available, or where the drive is more than a decade old and the control electronics are of similar age, the economics usually favour replacement — and the replacement can be specified at a more appropriate rating, which resets the thermal margin as well as the capacitors.

Whichever route is taken, document the new baseline at return to service. The next routine depends on it.

Safety, without exception

The DC link stores lethal energy and it stores it after the supply is removed. Safe isolation to BS 7671, a verified dead test, the manufacturer's stated discharge wait time, and a measured confirmation that the bus has fallen below the safe threshold — in that order, every time. A routine that treats the discharge wait as a formality is one that will eventually produce exactly the incident it was designed to prevent.

All Articles

Related Articles

A Reference Before the Fault: First-Week Vibration Capture for Bosch Motors

Current-Spectrum Triage: Using MCSA on Bosch-Driven Plant Without Overselling It

Current-Spectrum Triage: Using MCSA on Bosch-Driven Plant Without Overselling It

Cool Frame, Hot Trip: Verifying Overtemperature Alarms on Bosch Motors

Cool Frame, Hot Trip: Verifying Overtemperature Alarms on Bosch Motors